● Rated Current: 63-1600A
● Working Voltage: up to 690VAC~
● Poles Number: 3P, 4P
● Standard: IEC60947-3
The EDX series disconnector switch is designed for use in AC 50Hz electrical systems with a rated voltage of up to 660V and DC voltage up to 440V. It is primarily used in power distribution equipment in industrial enterprises, providing a means for infrequent switching, circuit breaking, and electrical isolation.
The EDX series disconnector switch complies with the IEC60947-3 and GB14048.3 standards, ensuring its adherence to international safety and performance requirements.
1. Altitude not more than 2000m.
2. The range of ambient temperature is from 5 degree to 40 degree .
3. Relative humidity not more than 95%.
4. The environment without any explosive medium.
5. The environment without any rain or snow attacking.
If the product is expected to be used in the environment where temperature is over +40 degree or below -5 degree to 40 degree , uses shall tell it to the manufacture.
● The switch adopts a modular design and is suitable for making and breaking circuits or electrical isolation. Above 1000A is only used for electrical isolation.
● The switch has 3 poles, 4 poles (3 poles + switchable neutral pole).
● There is a mark window under the switch to indicate the on-off state of the contact, and a rear observation window can be provided as required to directly observe the on-off state of the contact to ensure the reliability and safety of the switch operation.
● The handle can be directly installed on the switch for operation (referred to as in-cabinet operation), or it can be operated outside the power distribution cabinet door (referred to as out-of-cabinet operation) through the extension shaft, providing convenient operation.
● When the breaking position is "0", two to three locks can be used to lock the handle to prevent misoperation.
|
|
|||||||||
|
|
EDX-160 |
EDX-250A |
EDX-630A |
||||||
|
|
125 |
160 |
200 |
250 |
315 |
400 |
500 |
630 |
|
|
|
1000 |
1000 |
1000 |
||||||
|
|
2200 |
2200 |
2200 |
||||||
|
|
12 |
12 |
12 |
||||||
|
|
AC-21B |
125 |
160 |
200 |
250 |
315 |
400 |
500 |
630 |
|
AC-22B |
125 |
160 |
200 |
250 |
315 |
400 |
500 |
630 |
|
|
AC-23B |
125 |
160 |
200 |
250 |
315 |
400 |
500 |
630 |
|
|
|
400V |
63 |
80 |
100 |
132 |
160 |
220 |
280 |
315 |
|
Rated short-time endurance current lcw (kA Rms) 1s |
6 |
6 |
9 |
9 |
12.6 |
12.6 |
12.6 |
12.6 |
|
|
Rated breaking capacity Icn (A Rms) AC-23B 400V |
1000 |
1080 |
1600 |
2000 |
2520 |
3200 |
4000 |
5040 |
|
|
Rated switching capacity Icm (A Rms) AC-23B 400V |
1250 |
1600 |
2000 |
2500 |
3150 |
4000 |
5000 |
6300 |
|
|
Rated short-circuit switching capacity Icm (kA peak) |
9.2 |
9.2 |
15.3 |
15.3 |
25.2 |
25.2 |
25.2 |
25.2 |
|
|
Mechanical life 400V |
1400 |
1400 |
1400 |
1400 |
800 |
800 |
800 |
800 |
|
|
Electrical life 400V |
200 |
200 |
200 |
200 |
200 |
200 |
200 |
200 |
|
|
|
6.5 |
6.5 |
10 |
10 |
21 |
21 |
21 |
21 |
|
|
|
||||
|
|
EDX-1600A |
|||
|
|
1000 |
1250 |
1600 |
|
|
|
1000 |
|||
|
|
2200 |
|||
|
|
12 |
|||
|
|
AC-21B |
1000 |
1250 |
1600 |
|
AC-22B |
1000 |
1250 |
1600 |
|
|
AC-23B |
1000 |
1250 |
1600 |
|
|
|
400V |
560 |
560 |
560 |
|
Rated short-time endurance current lcw (kA Rms) 1s |
30 |
30 |
30 |
|
|
Rated breaking capacity Icn (A Rms) AC-23B 400V |
1500 |
1875 |
2400 |
|
|
Rated switching capacity Icm (A Rms) AC-23B 400V |
1500 |
1875 |
2400 |
|
|
Rated short-circuit switching capacity Icm (kA peak) |
63 |
63 |
63 |
|
|
Mechanical life 400V |
500 |
500 |
500 |
|
|
Electrical life 400V |
100 |
100 |
100 |
|
|
|
37 |
37 |
37 |
|
Clibeanna Te: